DBK208, pg. 6
987594 DBK Option Cards and Modules
DBK208
Board #
Switch S1 Configurations
Address
Designation in DaqView
(see notes 2 & 3)
16 8 4 2 Bank 0 Bank 1 Expanded Digital I/O in
Async Digital I/O window
Channel
0
OFF OFF OFF OFF 0 1 P2 0-A P2 0-B
1
OFF OFF OFF
ON
2 3 P2 0-C P2 0-D
0
2
OFF OFF
ON
OFF 4 5 P2 1-A P2 1-B
3
OFF OFF
ON ON
6 7 P2 1-C P2 1-D
1
4
OFF
ON
OFF OFF 8 9 P2 2-A P2 2-B
5
OFF
ON
OFF
ON
10 11 P2 2-C P2 2-D
2
6
OFF
ON ON
OFF 12 13 P2 3-A P2 3-B
7
OFF
ON ON ON
14 15 P2 3-C P2 3-D
3
8 ON
OFF OFF OFF 16 17 P2 4-A P2 4-B
9 ON
OFF OFF
ON
18 19 P2 4-C P2 4-D
4
10 ON
OFF
ON
OFF 20 21 P2 5-A P2 5-B
11 ON
OFF
ON ON
22 23 P2 5-C P2 5-D
5
12 ON ON
OFF OFF 24 25 P2 6-A P2 6-B
13 ON ON
OFF
ON
26 27 P2 6-C P2 6-D
6
14 ON ON ON
OFF 28 29 P2 7-A P2 7-B
15 ON ON ON ON
30 31 P2 7-C P2 7-D
7
Notes: (1) Switch S1 settings are made physically on the DBK208 boards and are checked in DaqView (see the
following screen capture). The software aspect is detailed on the following page.
(2) The Digital Option Cards External Connection section of DaqView’s Configure System Hardware
window lists 8 channels (0 through 7) as shown in the following screen image.
(3) Each of the 8 channels can represent 2 DBK208 boards. For example, as seen in the table, System Board
0 and System Board 1 would both show up in DaqView’s channel 0.
(4) In the Async Digital I/O window, each active channel (representing 2 boards) has divisions of A, B, C,
and D. A represents Bank 0 of the first board. B represents Bank 1 of the first board.
C represents Bank 0 of the second board. D represents Bank 1 of the second board.
(5) Banks are selected to be “Input” or “Output” via jumpers. Jumper JP0 applies to Bank 0, JP1 applies to
Bank 1.
Logic outputs provide signals for clocking data to registers for the Opto-22 SSR type modules. On-board
jumpers (JP0 and JP1) are used to set the banks for “input” or “output.” The banks can be set
independently, however, all modules within a bank will have the same setting. For example, JP0 could be
set to “Input,” configuring all 8 modules of Bank 0 to Input; and JP1 could be set to “Output,” configuring
all Bank 1 modules to “Output.”
Each Opto-22 module has a 2-connector terminal block for signal connections.