CB-7011/CB-7011D, CB-7018 Users Manual
2.23 @AAEAT
Description: Enable Alarm
Note: The command is for CB-7011/11D/11P/11PD only.
Syntax: @AAEAT[CHK](cr)
@ delimiter character
AA address of setting module (00 to FF)
EA command for enable alarm.
T alarm type, M=momentary alarm, L=latch alarm.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
Example:
Command: @01EAM Receive: ?01
Set address 01 momentary alarm, return success.
Related Command:
@AADA (Sec. 2.26), @AACA (Sec. 2.27) Related Topic:
High/Low Alarm (Sec. 3.6)