35
CB-7011/CB-7011D, CB-7018 User’s Manual
2.14 $AA9(Data)
Description: Set CJC Offset Value
Syntax: $AA9(Data)[CHK](cr)
$ delimiter character
AA address of setting module (00 to FF)
9 command for setting CJC offset value
(Data) CJC offset value comprises a sign and 4 hexadecimal
digits, from -1000 to +1000, each count is 0.01°C.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module (00 to FF)
Example:
Command: $019+0010 Receive: !01
Set address 01 CJC offset increase 16 counts (+0.16°C), re-
turn success.
Related Command:
$AA3 (Sec. 2.8)