CB-7011/CB-7011D, CD-7018 Users Manual
2.3 #AA
Description: Read Analog Input
Syntax: #AA[CHK](cr)
# delimiter character
AA address of reading module(00 to FF)
Response: Valid Command: >(Data)[CHK](cr)
Syntax error or communication error may yield no re-
sponse.
> delimiter for valid command
(Data) analog input value, reference Sec. 1.10 for its format.
For CB-7018/18P, the data is the combination for each chan-
nel respectively.
Example:
Command: #01 Receive: >+02.635
Read address 01, return data success.
Command: #02 Receive: >4C53
Read address 02, return data in HEX format success.
Command: #04
Receive: >+05.123+04.153+07.234-02.356+10.000-
05.133+02.345+08.234
Module address 04 is CB-7018. Read address 04, get analog
input data of eight channels.
Related Command:
%AANNTTCCFF (Sec. 2.1), $AA2 (Sec. 2.7)