61
CB-7012, CB-7014, CB-7017 Users Manual
2.38 ~AA1
Description: Reset Module Status
Syntax: ~AA1[CHK](cr)
~ Delimiter character
AA Address of module to set (00 to FF)
1 Command to reset module status
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
Example:
Command: ~010 Receive: !0104
Read Address 01 module status, return 04, host watchdog
timeout status is set.
Command: ~011 Receive: !01
Reset Address 01 module status; return successful.
Command: ~010 Receive: !0100
Read Address 01 module status, return 00, host watchdog
timeout status is clear.
Related Command:
Sec.2.36, ~**; Sec.2.37, ~AA0
Related Topic:
Set.3.2, Module Status; Sec.3.3, Dual Watchdog Operation